TECHNICAL SPEC · SYSTEM CONFIGURATION

Lighting control system configuration

In the lighting control system, every device hangs on a single RS485 line. The modules in the dimmer panel, the switches in each room, input modules that receive sensors, the setup PC and HA (home automation) all exchange ASCII commands on the same line. This page explains, with a diagram per circuit, how each module and switch is connected.

SPEC VERSION
SYSTEM_Rev03
BUS
RS485 2-wire
SPEED
9600 8N1
TOPOLOGY
Daisy chain
NODES / LINE
≤ 32
OVERVIEW

Overall configuration diagram

Inside the dimmer panel the modules are connected by RS485, and that line leaves the panel and extends to switches and sensors, the setup PC / HA and other dimmer panels. Select a circuit to highlight only its wiring and show its description.

Circuit
HA system Third-party HA equipment with RS485 RS485 2P Setup PC (direct connection) Excel / terminal software USB–RS485 adapter USB→RS485 Gateway PC RS485–USB + virtual COM port Wi-Fi / LAN Setup PC (remote) Setup while moving around Dimmer panel 1 RS485 (in panel) RS485 router RS485X · signal repeater Phase dimming FP01 + DIMX4 PWM dimming FP01 + PWMX4 ON/OFF relay FP01 + RELAYX8 Remote-control relay control RRX4 · remote-control switch + transformer DMX RS485X · DMX master Phase-dimming lighting fixtures Direct from the terminal block with VVF (L / N) PWM-dimming lighting fixtures Power ON/OFF + PWM dimming signal Non-dimming lighting fixtures ON/OFF only DMX lighting fixtures Canare DMX cable · fixture power supplied separately Red Blue Remote-control relay Installed in an external panel by the electrical contractor Task circuit (up to 20 A) Ordinary wall switches and lighting downstream FCPEV-S 3P A/B/SG + DC12V PLATE 001 PLATE 002 PLATE 003 Switches (each room, daisy-chained) INPUT 4ch Input module Occupancy sensor Wall switch etc. Elevator arrival, light level Dry a-contact · 1P Router (optional) Dimmer panel 2 Dimmer panel 3 … FCPEV-S 2P (A/B/SG + shield) Panels may be connected directly. Add a router when communication is unstable or when there are more than 32 devices
RS485 PLATFORM

Communication specification

Since all communication is RS485, the system is best understood as an “RS485 platform”. The protocol is ASCII without handshaking. Most HA equipment supports external RS485 devices, so it can be connected to the line as is and send commands.

StandardEIA RS-485
Circuit type2-wire, half-duplex (transmit and receive switch on the same pair)
Topology1:N multi-master (any node can transmit)
SynchronizationAsynchronous (start-stop)
Communication parameters9600bps / data length 8bit / parity none / stop bits 1
NodesUp to 32 RS485 transceivers per line. Split with a router if exceeded
Collision avoidanceBefore transmitting, check the receive buffer; if another node is transmitting, wait 5 ms + a random 0–10 ms and retry. No special protocol is required on the HA side
CableFCPEV-S 0.6 mm or 0.9 mm, 2P (between panels) / 3P (switch circuit). Always pair A and B on one twisted pair
CABLE & TERMINAL

Cables and terminals

Each circuit uses a specific cable. Only the switch circuit carries, in addition to the RS485 signals, the DC 12 V that powers the switches on the same cable.

SWITCH LINE

FCPEV-S 3P

ABSGDC+DC−Shield

Daisy-chain wiring panel → switch → switch → input module. Signals A and B, signal ground (SG) and DC 12 V power are each assigned one pair. Grounding the shield is recommended.

PANEL TO PANEL

FCPEV-S 2P

ABSGShield

Between dimmer panels, and to the HA and setup PC. No power is sent between panels, so only signals A and B, SG and the shield.

CONTACT INPUT

FCPEV-S 1P

3.3V OutInput n

Between the input module and sensors / relays. The module's 3.3 V passes through a dry a-contact and returns to an Input terminal.

REMOTE RELAY

KIV 0.5 or larger (red / blue)

R1–R8 redB blue (common)

From the dimmer panel to the remote-control relays in an external panel. Blue is the common wire permanently connected to the remote-control transformer; current on red switches each relay.

LOAD

VVF / Canare

LNDMX A/B/G

From the terminal blocks at the top of the dimmer panel to the lighting fixtures. VVF for the power of phase-dimming, ON/OFF and PWM fixtures; FCPEV 1P for the PWM dimming signal; Canare DMX cable for DMX.

SWITCH TERMINAL · 7P × 2 (IN / OUT)
IN (panel side, from the previous switch) OUT (daisy-chained to the next switch) + − A B G G E + − A B G G E Yellow pair: yellow = DC 12 V (+) / white = DC 12 V (−) Blue pair: blue = RS485 A / white = RS485 B Green pair: green and white = signal ground (SG) E: shield drain wire (connecting it improves noise immunity)

Terminals: 3.5 mm pitch, push-in type (spring cage), solid wire 0.5–1.0 mm², mating at 45° to the board. The IN and OUT sides are connected on the board, so the daisy-chain wiring continues directly to the next switch.

PANEL TERMINAL · panel terminal labels
Terminal labelSignalWire color
+ / −DC 12 V for switches (switch circuit terminal block only)Yellow / white
ARS485 signal ABlue
BRS485 signal BWhite (blue pair)
GSignal ground (SG)Green / white
EShield (drain wire)—

The panel terminal blocks are separated by circuit (inter-panel communication ABGE ABGE, HA communication ABG, switch communication +−ABGGE, etc.). Keep yellow/white, blue/white and green/white as pairs, and always connect the shield drain wire to E.

SWITCH

Switch configuration

A switch is a plate with a row of rotary encoder knobs that can be turned and pushed. Each plate has an address (plate number), and each knob has a button number and a group number; a knob operates the lighting circuits with the same group number.

PLATE · 3 / 5 / 7 KNOBS
Main board (3 knobs) Extension #1 (address 1) Extension #2 (address 2) FFC 16P 0.5mm FFC RS485 · DC 12 V on the main board terminal block only

3 knobs = main board only, 5 knobs = 1 extension, 7 knobs = 2 extensions. Extension boards connect by FFC (16-pole, 0.5 mm pitch, 35–40 mm, top contacts on both ends).

Plate numberAddress of each switch. Specified in commands as b001…
Button numberNumbers 1–7 for the knobs on the plate (from the top)
Group numberOne of 000–999 for each knob. Each lighting circuit stores the groups it belongs to and is operated by knobs with the same number
RotateRight for UP, left for DOWN. Stops at the module's upper and lower limits; turning does not switch off
PushON/OFF. The dimming % at OFF is saved in the module's EEPROM and restored at the next ON (kept through power failures)
Operating modeonof(ON/OFF toggle) / scns (scene recall) / na__ (no action). For a knob used as a scene button, turn its encoder OFF
SetupConnect a PC to the RS485 line and set up with commands in terminal software (Excel is not supported). Initial settings: number of buttons bxxxwvol, encoder ON/OFF bxxxency, mode bxxxmode
HardwareARM SoC (firmware updatable), isolated RS485 driver, DC 12 V input, LEDs showing knob status

Example: put all lighting circuits of the living room in group 005 and set a knob's group to 005 as well; that single knob then operates UP/DOWN/ON/OFF for the whole living room. The reference board is ROTARY03 + ROTARY02N.

INPUT MODULE

Input module

Monitors dry a-contacts such as occupancy sensors, elevator arrival signals and light sensors (EE switches), and sends contact changes as commands to RS485. It is daisy-chained on the same circuit as the switches and also takes its power from the communication cable.

WIRING · 40.5 × 40.5 mm
INPUT MODULE Relay of a sensor etc. Dry a-contact SHIELD B A SG DC− DC+ To FCPEV-S 3P

When the voltage from 3.3V Out returns to Input through the external relay contact, it is detected as “on”. The input stage is isolated by optoisolators.

TerminalDescription
3.3V Out ×2Voltage output for dry a-contacts. Returned to Input through a relay
Input1–4Input of the voltage returned from the contact (4 channels)
RS485 A ISO / B ISOIsolated RS485 terminals
0V ISOSignal GND (SG) of the isolated RS485
EarthShield
DC12V / POWER GNDPlus / minus of DC 12 V received from the switch circuit
Daisy-chain wiringBranch with a joint fitting outside the terminal block, or joint at the terminal block
LocationNear the sensor. Depending on the building, in the attic space etc.
SetupNo setup over RS485; the behavior is fixed in the firmware (direct connection to HA is also possible)

Mechanical relays are standard. When using an occupancy sensor for 100 VAC loads, insert an AC relay with a 100 VAC coil as a buffer. Solid-state relays only if matching tests can be performed.

COMMAND FLOW

Command flow

A switch sends only “which group, and what to do”. Every module receives the command and acts only if its circuit belongs to that group. This is why area-by-area operation is possible with a single cable.

01

Turn the knob one notch to the right

Turn the knob assigned to group 005.

02

Transmit to RS485

v005up__ These 8 characters travel over the whole line.

03

All modules receive

Each circuit checks its group table.

04

Only matching circuits act

Only the circuits of group 005 raise their brightness one step (up to the upper limit).

CommandExampleLengthAction
UPv001up__8Brighten the circuits of group 001 by one step. Sent when the knob is turned one notch right
DOWNv001down8Dim the circuits of group 001 by one step (stops at the lower limit). Knob turned one notch left
ONv001on__8Turn on at the dimming % saved last
OFFv001off_8Save the current dimming % and turn off
Scene callg001sccc000512Recall the dimming % of scene 5 in the scene table for each circuit of group 001
Fadeg001fade001012Set the fade time for scene calls to 1.0 s (kept in EEPROM). Sent just before a scene call

Sensors, input modules and HA send the same commands. The 8-character “v command” is a short message intended for continuous transmission from rotary encoders; at 9600 bps it takes about 7 ms, and a 12-character command about 10 ms.

INSTALLATION

Wiring notes

Most causes of unstable communication are in the wiring. Check the following points during installation.

Source: Lighting control system specification Rev03 (Ch. 1 System, Ch. 5 Switches, Ch. 6 Input module, Ch. 7 Drawings). The specification lists the ON/OFF module as RELAYX4; the current reference board is RELAYX8.